HRS Series Air-Cooled Refrigeration Type external appearance
Model | HRS012-A□-20 | HRS018-A□-20 | HRS024-A□-20 | HRS030-A□-20 | HRS050-A□-20 | HRS060-A□-20 | ||
---|---|---|---|---|---|---|---|---|
Cooling Method | Air-cooled refrigeration type | |||||||
Refrigerant | R407C (HFC) | R410A (HFC) | ||||||
Refrigerant Charge (kg) | 0.35 | 0.36 | 0.36 | 0.57 | 0.65 | 0.85 | ||
Control Method | PID control | |||||||
Ambient Operating Temperature / Humidity / Altitude*1 *12 | Temperature: 5 to 40°C, High-temperature environment specification (optional): 5 to 45°C, Humidity: 30 to 70%, Altitude: less than 3,000 m | |||||||
Circulating Fluid System | Circulating Fluid*2 | Clear water, 15% ethylene glycol aqueous solution*4 | ||||||
Set Temperature Range*1 (°C) | 5 to 40 | |||||||
Cooling Capacity*3 (50/60 Hz) (W) | 1,100/1,300 | 1,700/1,900 | 2,100/2,400 | 2,600/3,200 | 4,700/5,100 | 4,900/5,900 | ||
Heating Capacity*3 (50/60 Hz) (W) | 530/650 | 600/640 | 1,100/1,400 | 1,000/1,300 | ||||
Temperature Stability*5 (°C) | ±0.1 | |||||||
Pump | Rated Flow Rate*6 *7 (50/60 Hz) (L/min) | 7 (0.13 MPa) / 7 (0.18 MPa) | 23 (0.24 MPa) / 28 (0.32 MPa) | 23 (0.21 MPa) / 28 (0.29 MPa) | ||||
Maximum Flow Rate (50/60 Hz) (L/min) | 27/29 | 34/40 | 31/42 | 29/38 | ||||
Maximum Pump Head (50/60 Hz) (m) | 14/19 | 50 | ||||||
Output (W) | 200 | 550 | ||||||
Tank Capacity (L) | Approx. 5 | |||||||
Pipe Connection Port Diameter | Rc 1/2 | |||||||
Fluid Contacting Parts Material | Stainless steel, copper (heat exchanger brazing), bronze, alumina ceramic, carbon, PP, PE, POM, FKM, EPDM, PVC | |||||||
Electrical Systems | Power Supply | Single-phase 200 to 230 V AC (50/60 Hz) Allowable voltage variation ±10% | ||||||
Circuit Protector (A) | 10 | 20 | 30 | |||||
Compatible Earth Leakage Circuit Breaker Capacity*8 (A) | 10 | 20 | 30 | |||||
Rated Operating Current (A) | 4.6/5.1 | 4.7/5.2 | 5.1/5.9 | 5.2/6.0 | 8/11 | 8.9/11.5 | ||
Rated Power Consumption*3 (50/60 Hz) (kVA) | 0.9/1.0 | 0.9/1.0 | 1.0/1.2 | 1.0/1.2 | 1.7/2.2 | 1.8/2.3 | ||
Noise Level*9 (50/60 Hz) (dB) | 60/61 | 62/65 | 65/68 | 66/68 | ||||
Accessories | Pipe fitting (for drain outlet) 1 pc.*11, Input/output signal connector 1 pc., Power supply connector 1 pc.*11 Operation manual (for installation and operation) 1 pc., Quick manual (with a clear case) 1 pc.*11 Alarm code list sticker 1 pc., ferrite core (for communication) 1 pc. Power cable must be purchased separately or provided by the user. | |||||||
Weight*10 (kg) | 43 | 47 | 69 | 73 |
*Some values differ from the standard specifications due to optional features. See the catalog for details.
*1: Use in a condensation-free environment.
*2: If you are using clear water, please use water that meets the Japan Refrigeration and Air Conditioning Industry Association Water Quality Standards (JRA GL-02-1994: Cooling Water / Circulation Type / Supply Water).
*3: Values when: 1. Ambient operating temperature: 25°C, 2. Circulating fluid temperature: 20°C, 3. Rated flow rate of circulating fluid, 4. Circulating fluid: clear water. See the cooling capacity graphs in the catalog for details.
*4: If the circulating fluid temperature is below 10°C, use 15% ethylene glycol aqueous solution.
*5: Outlet temperature when the circulating fluid is at rated flow rate, and the outlet and return port are connected. When the installation environment and power supply are within the specification range and stable.
*6: The capacity at the outlet of this device when the circulating fluid temperature is 20°C.
*7: Minimum flow rate required to maintain cooling capacity, temperature stability, etc. Below the rated flow rate, the cooling capacity and temperature stability may not meet specifications. (In that case, use a bypass piping set [sold separately].
*8: To be provided by the customer. Use an earth leakage circuit breaker with a current sensitivity of 30 mA. (An option with an earth leakage circuit breaker [symbol B] is also available.)
*9: When front 1 m, height 1 m, stable with no load. See *3 for other conditions.
*10: Weight in a dry state without circulating fluid.
*11: Not included with the HRS050/060.
*12: For altitudes above 1,000 m, please refer to "*For altitudes above 1,000 m" in Section 14 "Operating Environment and Storage Environment," on p. 64 of the catalog.
HRS Series Water-Cooled Refrigeration Type external appearance
Model | HRS012-W□-20 | HRS018-W□-20 | HRS024-W□-20 | HRS030-W□-20 | HRS050-W□-20 | HRS060-W□-20 | ||
---|---|---|---|---|---|---|---|---|
Cooling Method | Water-cooled refrigeration type | |||||||
Refrigerant | R407C (HFC) | R410A (HFC) | ||||||
Refrigerant Charge (kg) | 0.3 | 0.31 | 0.31 | 0.5 | 0.65 | 0.75 | ||
Control Method | PID control | |||||||
Ambient Operating Temperature / Humidity / Altitude*1 | Temperature: 5 to 40°C, Humidity: 30 to 70%, Altitude: Less than 3,000 m | |||||||
Circulating Fluid System | Circulating Fluid*2 | Clear water, 15% ethylene glycol aqueous solution*4 | ||||||
Set Temperature Range*1 (°C) | 5 to 40 | |||||||
Cooling Capacity*3 (50/60 Hz) (W) | 1,100/1,300 | 1,700/1,900 | 2,100/2,400 | 2,600/3,200 | 4,700/5,100 | 4,900/5,900 | ||
Heating Capacity*3 (50/60 Hz) (W) | 530/650 | 400/600 | 1,000/1,300 | |||||
Temperature Stability*5 (°C) | ±0.1 | |||||||
Pump | Rated Flow Rate*6 *7 (50/60 Hz) (L/min) | 7 (0.13 MPa) / 7 (0.18 MPa) | 23 (0.24 MPa) / 28 (0.32 MPa) | 23 (0.21 MPa) / 28 (0.29 MPa) | ||||
Maximum Flow Rate (50/60 Hz) (L/min) | 27/29 | 34/40 | 31/42 | 29/38 | ||||
Maximum Pump Head (50/60 Hz) (m) | 14/19 | 50 | ||||||
Output (W) | 200 | 550 | ||||||
Tank Capacity (L) | Approx. 5 | |||||||
Pipe Connection Port Diameter | Rc 1/2 | |||||||
Fluid Contacting Parts Material | Stainless steel, copper (heat exchanger brazing), bronze, alumina ceramic, carbon, PP, PE, POM, FKM, EPDM, PVC | |||||||
Heat-Dissipating Water System | Temperature Range (°C) | 5 to 40 | ||||||
Pressure Range (MPa) | 0.3 to 0.5 | |||||||
Required Flow Rate*11 (50/60 Hz) (L/min) | 8 | 12 | 14 | 15 | 16 | 17 | ||
Inlet-Outlet Pressure Differential of Heat-Dissipating Water (MPa) | 0.3 or more | |||||||
Pipe Connection Port Diameter | Rc3/8 | Rc 1/2 | ||||||
Fluid Contacting Parts Material | Stainless steel, copper (heat exchanger brazing), bronze, synthetic rubber | |||||||
Electrical Systems | Power Supply | Single-phase 200 to 230 V AC (50/60 Hz) Allowable voltage variation ±10% | ||||||
Circuit Protector (A) | 10 | 20 | ||||||
Compatible Earth Leakage Circuit Breaker Capacity*8 (A) | 10 | 20 | ||||||
Rated Operating Current (A) | 4.6/5.1 | 4.7/5.2 | 5.1/5.9 | 5.2/6.0 | 7.6/10 | 7.6/10.4 | ||
Rated Power Consumption Note 3) (50/60 Hz) kVA | 0.9/1.0 | 0.9/1.0 | 1.0/1.2 | 1.0/1.2 | 1.5/2.0 | 1.5/2.1 | ||
Noise Level*9 (50/60 Hz) (dB) | 60/61 | 62/65 | 65/68 | 66/68 | ||||
Accessories | Pipe fitting (for drain outlet) 1 pc.*12, Input/output signal connector 1 pc., Power supply connector 1 pc.*12 Operation manual (for installation and operation) 1 pc., Quick manual (with a clear case) 1 pc.*12 Alarm code list sticker 1 pc., ferrite core (for communication) 1 pc. Power cable must be purchased separately or provided by the user. | |||||||
Weight*10 (kg) | 43 | 46 | 67 |
*Some values differ from the standard specifications due to optional features. See the catalog for details.
*1: Use in a condensation-free environment.
*2: If you are using clear water, please use water that meets the Japan Refrigeration and Air Conditioning Industry Association Water Quality Standards (JRA GL-02-1994: Cooling Water / Circulation Type / Supply Water).
*3: Values when: 1. Ambient operating temperature: 25°C, 2. Circulating fluid temperature: 20°C, 3. Rated flow rate of circulating fluid, 4. Circulating fluid: clear water, 5. Heat-dissipating water temperature: 25°C. See the cooling capacity graphs in the catalog for details.
*4: If the circulating fluid temperature is below 10°C, use 15% ethylene glycol aqueous solution.
*5: Outlet temperature when the circulating fluid is at rated flow rate, and the outlet and return port are connected. When the installation environment and power supply are within the specification range and stable.
*6: The capacity at the outlet of this device when the circulating fluid temperature is 20°C.
*7: Minimum flow rate required to maintain cooling capacity, temperature stability, etc.
Below the rated flow rate, the cooling capacity and temperature stability may not meet specifications. (In that case, use a bypass piping set [sold separately].)
*8: To be provided by the customer. Use an earth leakage circuit breaker with a current sensitivity of 30 mA. (An option with an earth leakage circuit breaker [symbol B] is also available.)
*9: When front 1 m, height 1 m, stable with no load. See *3 for other conditions.
*10: Weight in a dry state without circulating fluid.
*11 Required flow rate when the circulating fluid temperature is 20°C, the circulating fluid is at the rated flow rate, the heat-dissipating fluid is 25°C and the listed cooling capacity load is applied.
*12: Not included with the HRS050/060.
HRS012/018-A/W-10 (single-phase 100/115 V AC) pump capacity
HRS-012/018/024-A/W-20 (single-phase 200 to 230 V AC) pump capacity
Mechanical seal details
Notes
*The pump used in the Thermo-Chiller HRS050/060 Series uses a mechanical seal with a fixed ring and a rotating ring in the shaft seal. If foreign matter enters the gap in the seal, it could cause issues such as seal leakage, pump lock, etc., so it is highly recommended that a particle filter is installed on the chiller return piping.
(Unit: mm)
HRS012/018/024 dimensions/diagram
HRS030-A-20 dimensions/diagram
HRS030-W-20 dimensions/diagram
HRS050/060-A dimensions/diagram
HRS050/060-W dimensions/diagram
Référence pièce
|
---|
HRS024-A-20-T |
HRS024-W-20-T |
Référence pièce | Relatif à |
Prix unitaire standard
| Quantité minimale de commande | Remise sur volume | Capacité de refroidissement | Type de filetage de tuyauterie | Spécifications en option | |
---|---|---|---|---|---|---|---|---|
8,236.46 € | 1 | 14 jours | 2100/2400W (50/60Hz) | Rc | Spécifications de tête de pompe surélevée | |||
- | 8,566.71 € | 1 | 98 jours | 2100/2400W (50/60Hz) | Rc | Spécifications de tête de pompe surélevée |
Loading...
Configurer
Propriétés de base
Type
Capacité de refroidissement
Type de filetage de tuyauterie
Spécifications en option
Filtrer par type de données CAO
Filtrer par jours d'expédition standard
Propriétés optionnelles